MengziShielded (Unshielded) Top-Expansion Busbar

Shielded flexible busbar connectors are used for busbar connections between SF6-insulated metal-enclosed switchgear. They provide fully sealed and fully insulated connections between load switches and busbars, completely eliminating the fatal risks associated with high-voltage conductors being exposed to harsh weather conditions. In addition, they are easy to install and offer high reliability.

Product Description

  Product Overview

  Shielded flexible busbar connectors are used for busbar connections between SF6-insulated metal-enclosed switchgear. They provide fully sealed and fully insulated connections between load switches and busbars, completely eliminating the fatal risks associated with high-voltage conductors being exposed to harsh weather conditions. In addition, they are easy to install and offer high reliability.

  The busbar connector is composed of a busbar combined with T-shaped and cross-shaped connectors. The busbar length can be custom-made anywhere between 300 mm and 800 mm, making it suitable for electrical systems rated at 8.7/15 kV to 12/24 kV with rated currents of 630 A or 1250 A. The bushing interfaces comply with DIN 47636, EN 50180, and EN 50181 standards.

11  1

A T-joint B Busbar connection C Cross joint

  Electrical Performance

Testing Items

Testing Standards

Rated voltage

15kV

24kV

Applicable Casing Types

Type C

Type C

Power-frequency withstand voltage (AC)

42kV/1min

65kV/5min

Partial discharge

18 kV, ≤10 pC

22 kV, ≤10 pC

Impulse voltage (10 cycles for each polarity)

95kV

125kV

Shunt resistor

≤3000Ω

≤3000Ω

  Structural dimensions

1