ZW32-12kV Pole-Mounted Vacuum Circuit Breaker
The ZW32-12 outdoor high-voltage vacuum pole-mounted circuit breaker (hereinafter referred to as the “circuit breaker”) is a control and protection device for 12 kV, 50 Hz three-phase AC high-voltage distribution networks. It is primarily used to interrupt and make connections of load currents, overload currents, and short-circuit currents in power lines.
Keywords: High- and low-voltage complete sets – packaged substations – ring main units
Category:
Contact Us
Product Description
Product Overview
The ZW32-12 outdoor high-voltage vacuum pole-mounted circuit breaker (hereinafter referred to as the “circuit breaker”) is a control and protection device for 12 kV, 50 Hz three-phase AC high-voltage distribution networks. It is primarily used to disconnect and make contact with load currents, overload currents, and short-circuit currents in power lines.
Applicable Advantages and Scope of Application
● The main advantages include compact size, light weight, easy installation, simple operation, high reliability, and long service life, making them particularly well suited to applications involving frequent switching. They are especially ideal for installation and use in rural power grids where maintenance and repair capabilities are limited. They can also serve as sectionalizing switches in the distribution network, and when equipped with a controller, they can enable distribution automation.
● Supplying power at the 20 kV voltage level offers a range of advantages, including increased power supply capacity, guaranteed voltage quality, reduced power losses in the grid, and lower grid construction costs.
● Suitable for the construction and renovation of power equipment in urban distribution networks, rural distribution networks, mines, railways, and other applications. Used for protection and control in substation and industrial/mining enterprise distribution systems.
Main Technical Parameters of the Product
|
Serial Number |
Name |
Unit |
Numerical value |
|
|
1 |
Rated voltage |
kilovolt |
12 |
|
|
2 |
Rated current |
A |
630 |
|
|
3 |
Rated frequency |
Hertz |
50 |
|
|
4 |
Rated thermal stability current |
kA |
20/25 |
|
|
5 |
Rated short-circuit breaking current |
kA |
20/25 |
|
|
6 |
Rated dynamic stability current (peak) |
kA |
50/63 |
|
|
7 |
Rated Short-Circuit Making Current (Peak) |
kA |
50/63 |
|
|
8 |
Thermal stability time |
S |
4 |
|
|
9 |
Rated Operating Sequence |
S |
O-0.3s-CO-180s-C |
|
|
10 |
Rated Insulation Level |
1-minute power-frequency withstand voltage between phases and to ground/open circuit |
kilovolt |
42/48 |
|
Rated lightning impulse withstand voltage (peak), phase-to-phase, phase-to-ground, and across gaps |
75/85 |
|||
|
1-minute power-frequency withstand voltage of the secondary circuit |
2 |
|||
|
11 |
Mechanical life |
next |
10000 |
|
|
12 |
Rated short-circuit breaking current breaking operations |
30 |
||
|
13 |
Rated Current Interrupting Capacity |
10000 |
||