ZW20-12 Type Pole-Mounted Circuit Breaker
The ZW20-12F/T–LO–LO series outdoor high-voltage vacuum circuit breaker (hereinafter referred to as the “circuit breaker”) is an outdoor distribution device with a rated voltage of 12 kV and a three-phase AC frequency of 50 Hz.
Keywords: High- and low-voltage complete sets – packaged substations – ring main units
Category:
Contact Us
Product Description
Product Overview
The ZW20-12F/T LO-LO series outdoor high-voltage vacuum circuit breaker (hereinafter referred to as the “circuit breaker”) is an outdoor distribution device with a rated voltage of 12 kV and a three-phase AC frequency of 50 Hz.
Product Features
The enclosure incorporates VSP5–derived gas-sealing, explosion-proof, and insulation-encapsulation technologies, and the incoming and outgoing cable conduits have also been upgraded for enhanced sealing performance, resulting in excellent overall sealing. The SF6 gas充装 inside remains completely leak-free and is unaffected by external environmental conditions. The spring-operated mechanism has been miniaturized and optimized for greater reliability and stability, featuring a direct-chain primary drive and a multi-stage tripping system, which improve operational reliability and stability by several times compared with conventional domestic spring-operated mechanisms. Furthermore, the contact between the shaft and bushing in the main circuit adopts an internal-retracting, external-expanding link-type structure, ensuring low contact resistance and minimal temperature rise. Consequently, the ZW20-12F outdoor pole-mounted vacuum circuit breaker is a maintenance-free product.
Main Technical Parameters of the Product
| Serial Number | Project | Unit | Data | ||
| 01 | Rated voltage | kilovolt | 12 | ||
| 02 | Rated frequency | Hertz | 50 | ||
| 03 | Rated current | A | 630 | 1250 | |
| 04 | Rated short-circuit breaking current | kA | 20 | 25 | |
| 05 | Rated Peak Withstand Current | kA | 50 | 63 | |
| 06 | Rated short-time withstand current | kA | 20 | 25 | |
| 07 | Rated short-circuit making current | kA | 50 | 63 | |
| 08 | Rated Operating Sequence | Break - 0.3s - Close - 180s - Close | |||
| 09 | Mechanical life | next | 10000 | ||
| 10 | Rated Current Interrupting Capacity | next | 10000 | ||
| 11 | Rated short-circuit breaking operations | next | 30 | ||
| 12 | Power-frequency withstand voltage for 1 minute | (Wet) phase-to-ground | kilovolt | 34 | |
| (Dry) phase-to-phase, phase-to-ground/open-circuit | kilovolt | 42/48 | |||
| 13 | Lightning Impulse Withstand Voltage | Phase-to-phase, phase-to-ground/breaker contacts | kilovolt | 75/85 | |
| 14 | 1-minute power-frequency withstand voltage of the secondary circuit | v | 2000 | ||
| 15 | Quality | kilogram | Approximately 140 | ||
| 16 | Contact opening distance | mm | 9±1 | ||
| 17 | Contact travel | mm | 2.5±0.5 | ||
| 18 | Average tripping speed | millisecond | 1.2±0.2 | ||
| 19 | Average closing speed | m/s | 0.6±0.2 | ||
| 20 | Rated operating voltage | v | AC/DC220 | ||
| 21 | SF6 gas rated pressure (gauge pressure) | megapascal | 0 | ||