Shielded (Unshielded) Top-Expansion Busbar
Shielded flexible busbar connectors are used for busbar connections between SF6-insulated metal-enclosed switchgear. They provide fully sealed and fully insulated connections between load switches and busbars, completely eliminating the fatal risks associated with high-voltage conductors being exposed to harsh weather conditions. In addition, they are easy to install and offer high reliability.
Keywords: High- and low-voltage complete sets – packaged substations – ring main units
Category:
Contact Us
Product Description
Product Overview
Shielded flexible busbar connectors are used for busbar connections between SF6-insulated metal-enclosed switchgear. They provide fully sealed and fully insulated connections between load switches and busbars, completely eliminating the fatal risks associated with high-voltage conductors being exposed to harsh weather conditions. In addition, they are easy to install and offer high reliability.
The busbar connector is composed of a busbar combined with T-shaped and cross-shaped connectors. The busbar length can be custom-made anywhere between 300 mm and 800 mm, making it suitable for electrical systems rated at 8.7/15 kV to 12/24 kV with rated currents of 630 A or 1250 A. The bushing interfaces comply with DIN 47636, EN 50180, and EN 50181 standards.


A T-joint B Busbar connection C Cross joint
Electrical Performance
|
Testing Items |
Testing Standards |
|
|
Rated voltage |
15kV |
24kV |
|
Applicable Casing Types |
Type C |
Type C |
|
Power-frequency withstand voltage (AC) |
42kV/1min |
65kV/5min |
|
Partial discharge |
18 kV, ≤10 pC |
22 kV, ≤10 pC |
|
Impulse voltage (10 cycles for each polarity) |
95kV |
125kV |
|
Shunt resistor |
≤3000Ω |
≤3000Ω |
Structural dimensions