XGN□-12 Type AC Metal-Enclosed Switchgear (Air-Insulated)
Keywords: High- and low-voltage complete sets – packaged substations – ring main units
Category:
Contact Us
Product Description
Product Definition
This product is suitable for single-bus, double-bus, and single-bus with bypass systems in power applications, with rated voltages ranging from 3.6 to 12 kV, three-phase AC at 50 Hz, and rated currents from 630 A to 3,150 A, serving the functions of receiving and distributing electrical energy. It can meet the operational requirements of various types of power plants, substations, and industrial and mining enterprises.
Main Application Environment of the Product
Ambient air temperature: -10 to +40°C;
Altitude: 1,000 m and below;
Humidity conditions: the monthly average shall not exceed 95%, and the daily average water vapor pressure shall not exceed 2.2 kPa;
The monthly average shall not exceed 90%, and the monthly average water vapor pressure shall not exceed 1.8 kPa;
Seismic intensity: not exceeding 8 degrees;
Locations free from significant contamination by corrosive or flammable gases, etc.;
Main Technical Parameters of the Product
|
Project |
Parameters |
Project |
Parameters |
|
Rated voltage kV |
12 |
Rated short-time power-frequency withstand voltage (interrupting gap) kV |
49 |
|
Rated current A |
630 |
Rated Lightning Impulse Withstand Voltage (Breaker Contact) kV |
85 |
|
Rated Frequency Hz |
50 |
Mechanical life (cycles) |
2000 |
|
Rated active load breaking current A |
630 |
Circuit resistance μΩ |
≤200 |
|
Rated Closed-Loop Breaking Current A |
630 |
Rated cable charging and breaking current A |
10 |
|
Rated short-circuit making current (peak value) kA |
50 |
Rated short-time withstand current duration, in seconds |
3 |
|
Rated short-time withstand current A |
20 |
Rated peak withstand current kA |
50 |
|
Rated short-time power-frequency withstand voltage, kV |
42 |
Rated lightning impulse withstand voltage, kV |
75 |