XGN□-24 Type AC Metal-Enclosed Switchgear (abbreviated as C-GIS)
Keywords: High- and low-voltage complete sets – packaged substations – ring main units
Category:
Contact Us
Product Description
Product Overview
The XGN□-24 (SF18-24) gas-insulated high-voltage AC metal-enclosed switchgear (SF6 gas-insulated cabinet) is a new-generation, fully enclosed stainless-steel gas-insulated switchgear manufactured using advanced welding, gas charging, and leak-testing technologies. All live components are sealed within a stainless-steel enclosure filled with SF6 gas, and both the gas compartment and the fuse cartridge achieve an IP67 protection rating. Featuring a modular design, it is compact yet highly configurable and scalable, allowing for flexible configuration of combined electrical units and circuit-breaker units. This product is widely used in the construction and renovation of urban power grids, suitable for ring-network and terminal power supply in various distribution systems, and also ideal for integration into prefabricated substations and switchgear stations. It boasts fully enclosed construction, maintenance-free operation, a compact structure, and high reliability.
Product Notes
Note:
1. The parameters of the circuit breaker unit are determined by the intrinsic parameter values of the circuit breaker itself;
2. The relevant parameters of the switchgear unit depend on the rating values of the fuse.
Main Technical Parameters of the Product
|
Project |
Parameters |
Project |
Parameters |
|
Rated voltage kV |
24 |
Rated short-time power-frequency withstand voltage (interrupting gap) kV |
79 |
|
Rated current A |
1250 |
Rated lightning impulse withstand voltage (interrupter) peak kV |
145 |
|
Rated frequency Hz |
50 |
Classification levels based on mechanical life |
M2 |
|
Rated short-circuit breaking current kA |
25 |
According to the classification level of electrical life |
E2 |
|
Rated short-circuit making current kA peak |
63 |
Classification levels based on the switching capacity for capacitive current |
C2 |
|
Rated short-time withstand current duration, s |
4 |
Rating of auxiliary contacts |
2 |
|
Rated short-time withstand current kA |
25 |
Closing Operation Voltage V (Maximum/Rated/Minimum) |
AC242/220/187 |
|
Rated peak withstand current kA peak |
63 |
Trip Operation Voltage V (Maximum/Rated/Minimum) |
AC242/220/143 |
|
Rated cable charging and breaking current A |
25 |
SF6 gas rated filling pressure (gauge pressure at 20°C) MPa |
0.045 |
|
Rated line charging make-and-break current A |
10 |
Minimum operating pressure of SF6 gas (gauge pressure at 20°C): MPa |
0.02 |
|
Rated short-time power-frequency withstand voltage, kV |
65 |
Rated lightning impulse withstand voltage, kV peak |
125 |